Unicont SPb PCH-205 Spécifications Page 8

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 27
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 7
Unicont SPb Ltd Operating manual BCP-136
Page 8
6. Controls and indicators
Battery panel is equipped with the following controls and indicators:
control buttons,
selected battery LEDs (BAT1/2),
alarm LEDs (BAT ALARM 1/2, AC ALARM 1/2),
two digital LED indicators.
Arrangement of indicators:
Fig. 2 Arrangement and general purpose of indicators.
o Control buttons are used to select battery 1 or 2 to display its parameters by means
of the digital indicators, acknowledge alarm sound signals, perform the lamp test, adjust
brightness of LEDs and digital indicators. Menu navigation buttons make it possible to configure
CH-105 and PCH-205 (connected to digital interfaces) and to adjust shunt and alarm settings
(control button purposes are summarized in Table 3).
Table 3. Purposes of BCP-136 control buttons
Button Purpose
MENU
selection of main menu items (ref. section 8.3).
and
adjustment of LED brightness, selection of menu item values
ENTER
saving (entering) of the selected menu item value (ref. section 8.3).
BAT 1/2
selection of battery 1 or 2 (ports PORT1 and PORT2) for indication.
MUTE/TEST
switching off (acknowledging) of alarm sound signal (ref. section8.3.9), testing of
LEDs, indicators and the beeper (the test mode, ref. section 8.3.8)
o Alarm LEDs BAT ALARM and AC ALARM (ref. Fig. 2).
Table 4. Purposes of state indication LEDs.