Unicont SPb Ltd Operating manual BCP-136
Page 9
LED indicator Purpose
BAT ALARM
1 (PORT 1)
– if a digital interface is used (along with CH-105 or PCH-205), the
LED is switched on in case of alarm conditions (ref. CH-105 and PCH-
205 operating manuals, section "Alarms"),
– if an analog interface is used (along with SB-138), the LED is
switched on in case of a deviation from specified charge/discharge
parameters.
2 (PORT 2)
AC ALARM
1 (PORT 1)
– the LED is switched on in case of power supply failure of the battery
charger connected the corresponding panel port,
– the LED is switched on in case of potential-free (dry) contacts
disconnection of the relay connected to the corresponding panel port.
2 (PORT 2)
o LEDs BAT1 and BAT2 indicate the selected battery number (1 or 2), parameters of
which are currently shown by digital LED indicators.
o Digital LED indicators show actual values of battery current and voltage. Negative
sign on the LED indicator means negative (discharge) current.
o Residual battery capacity indicator shows residual capacity (power) of the selected
battery. (Currently not in use).
In the standby (primary) operating mode the battery panel indicators display the
following information: selected battery number, actual voltage (the left indicator) and
discharge/charge current (the right indicator) of the selected battery.
If CH-105 or PCH-205 is connected to the digital interface of the battery panel, which
operates in the standby (primary) mode, pressing on ENTER results in that letter "t" appears on
the left digital indicator, while the right one displays actual battery temperature. This function is
supported, provided that that CH-105 or PCH-205 is equipped with a DTS-135 battery
temperature sensor (ref. section 8.3.10 for detailed information). If such sensor is not installed,
the right indicator will display symbols "– – –".